|
Top Document: Electrical Wiring FAQ (Part 2 of 2) Previous Document: How to wire 3-way and 4-way switches Next Document: Where must outlets and switches be in bathrooms? See reader questions & answers on this topic! - Help others by sharing your knowledge
The NEC requires at least two 20 amp ``small appliance
circuits'' for kitchen counters. The CEC requires split-duplex
receptacles. Outlets must be installed such that no point is more
than 24" (NEC) (900 mm CEC) from an outlet. Every counter wider
than 12" (NEC) or 300 mm (CEC) must have at least one outlet.
The circuit these outlets are on may not feed any outlets except
in the kitchen, pantry, or dining room. Furthermore, these circuits
are in addition to any required for refrigerators, stoves, microwaves,
lighting, etc.
New rule (1996 NEC): all counter outlets must be GFCI protected.
(Old NEC rule for historical purposes) Non-dedicated outlets within
6' of a sink *must* be protected by a GFCI.
Split duplex receptacles are fed with a 220V circuit. The tab
is broken on the hot side of the outlet, and one hot goes to
the upper outlet, and the other hot goes to the lower outlet.
The neutral connects to both outlets through one screw. When
"carrying through" to another outlet, the neutral must be
pigtailed, such that removing the outlet, or having the neutral
connection fall off or burn out doesn't cause the neutral to
disconnect from downstream outlets ("loose neutral" problems -
see "What does it mean when the lights brighten...").
Top Document: Electrical Wiring FAQ (Part 2 of 2) Previous Document: How to wire 3-way and 4-way switches Next Document: Where must outlets and switches be in bathrooms? Part1 - Part2 - Single Page [ Usenet FAQs | Web FAQs | Documents | RFC Index ] Send corrections/additions to the FAQ Maintainer: clewis@ferret.ocunix.on.ca (Chris Lewis)
Last Update November 21 2011 @ 12:58 AM
|

I bought a new receptacle and installed the same. I still have no power I suspect there could be a bigger problem,this is aluminum wiring.
I've killed the breaker and call an electrician but am curious as to what happened.P.s. there is a dimmer switch on the same circuit.